Approved Document B Volume 2: Firestopping Guidance Explained
Approved Document B Volume 2 is government guidance on meeting Building Regulations fire safety requirements for buildings other than dwellings; designers of mixed-use buildings that include dwellings should also consult Volume 1. It gives guidance on compartmentation, cavity barriers and firestopping, while allowing alternative methods that provide at least the same overall level of safety.

Approved Document B Volume 2 is government guidance on meeting the Building Regulations' fire safety requirements for every covered building type other than dwellings. For offices, schools, hospitals, hotels and mixed-use premises, it gives guidance on compartmentation, cavity barriers and firestopping. Designers of mixed-use buildings with dwellings should also consult Volume 1. Under Requirement B3, the guidance addresses fire separation and the restriction of hidden fire and smoke spread in cavities.
What is Approved Document B?
Approved Document B is the government guidance that accompanies the fire safety requirements in the Building Regulations 2010. It comes in two volumes: Volume 1 covers only dwellings, including blocks of flats, and Volume 2 covers every other type of building the Building Regulations apply to, according to the Approved Document B Volume 2 (2026 amendments version).
Under Requirement B3 in the Building Regulations, Approved Document B Volume 2 aims to make sure that in a fire the building does not collapse early, there is enough fire separation inside it and from neighbouring buildings, automatic fire suppression is fitted where needed, and hidden spread of fire and smoke in cavities is restricted.
The legal requirement B3(4) in the Building Regulations 2010, Schedule 1 says a building must be designed and built so that unseen spread of fire and smoke in concealed spaces in its structure and fabric is inhibited. Volume 2 gives related guidance on firestopping and cavity barriers intended to restrict hidden fire and smoke spread.
Approved Document B is one route to satisfying the fire safety requirements; an alternative route is allowed if it provides no lower overall level of safety. The people doing the work must show that they comply, whichever approach they take.
What is firestopping?
Firestopping is the sealing of gaps caused by imperfect fit or design tolerance between building elements or components, to restrict the spread of fire and smoke. The definition describes a seal intended to restrict the spread of both fire and smoke through those gaps.
Every joint, imperfect fit and service opening through a fire-separating element should be sealed with fire-stopping so the element's fire resistance is not reduced. The guidance also says service openings should be as few as possible and as small as practicable.
Cavity barriers are a separate measure. They divide cavities and close their edges, and they are not the same thing as fire-stopping details. The guidance treats cavity barriers and firestopping as distinct details for controlling fire spread in concealed spaces.
At Skyline Firestopping, our installation teams seal service penetrations, linear gaps and joints through fire-rated walls and floors, using tested systems that maintain the required fire resistance periods.
What does Approved Document B Volume 2 need for firestopping?
Approved Document B Volume 2 gives guidance on where firestopping should be used and how its materials should be supported. These provisions appear in paragraphs 10.24 to 10.29 and in the compartmentation sections of the document.
Joints between fire-separating elements should be fire-stopped. Openings through a fire-resisting element for pipes, ducts, conduits or cables should be as few as possible, as small as practicable, and fire-stopped while still allowing pipes and ducts to move with heat. Each opening should be kept as small as practicable without preventing pipes and ducts from moving with heat.
Fire-stopping materials should be reinforced or supported by materials rated class A2-s3, d2 or better where the unsupported span is over 100 mm, or where non-rigid materials are used, unless fire resistance testing shows the non-rigid material is suitable. The stated purpose of that reinforcement or support is to prevent displacement.
Proprietary, tested fire-stopping and sealing systems may be used, but different materials suit different situations and not all of them are suitable everywhere. A proprietary system may be used only where its material is suitable for the particular situation.
Effective compartmentation needs fire resistance that is continuous at the joins between the elements forming a compartment. Any openings between compartments must not reduce that fire resistance. Where a compartment wall or floor meets another compartment wall or an external wall, its fire resistance should be maintained using fire-stopping that meets paragraphs 10.24 to 10.29.
A line of compartment walls cannot be completed by fitting cavity barriers above them. The compartment wall should go all the way up to the underside of the floor or roof above. At junctions with another compartment wall or an external wall, fire resistance should be maintained with firestopping that meets paragraphs 10.24 to 10.29.
Cavity barriers should be tightly fitted to rigid construction and mechanically fixed. Where that is not possible, such as where they meet slates, tiles or corrugated sheeting, the junction should be fire-stopped. At those irregular junctions, the guidance calls for firestopping because a tight fit to rigid construction is not possible.
Cavity barriers should divide or close cavities, while firestopping should be used at a junction where a tight fit to rigid construction is not possible.
What do you need to do for Approved Document B fire safety?
For a mixed-use building that includes dwellings, designers should use Approved Document B Volume 1 as well as Volume 2. The additional consultation applies because Volume 1 deals with dwellings while Volume 2 deals with other building types.
Following Approved Document B will probably satisfy the fire safety requirements, but other ways of complying are allowed if they give at least the same level of safety. Whichever route is used, those undertaking the work remain responsible for demonstrating compliance.
The Building Regulations do not impose requirements on how a building is managed once in use. However, the management regime should be kept up and risk-assessed for any change. Changes to that regime should be risk-assessed, and poor management may lead to prosecution of an employer, owner or occupier under the Fire Safety Order.
For new buildings, extensions or changes of use, fire safety information should be handed to the responsible person or accountable person when the project is complete or when the building is first occupied, whichever comes first. After occupation, any change to the building's management regime should be covered by a suitable risk assessment.
The maintenance duty applies where it is necessary to safeguard relevant persons. This ongoing duty applies throughout the building's life, not just at handover.
Who is responsible for fire safety?
The responsible person under the Fire Safety Order is the employer for a workplace they control. For other premises it is the person who controls the premises for a business or other undertaking, or otherwise the owner.
Under the Fire Safety Order, the responsible person must make a suitable and sufficient fire risk assessment to identify the general fire precautions they need to take. The assessment must be suitable and sufficient for identifying the general fire precautions needed to protect relevant persons.
Where necessary for safety, the responsible person must keep the premises and their fire safety facilities, equipment and devices under a suitable system of maintenance, in efficient working order and in good repair. Covered premises, facilities, equipment and devices must be kept in efficient working order and good repair under a suitable maintenance system.
Once a building is in use, its management regime falls outside the requirements imposed by the Building Regulations. Failing to do so may lead to prosecution of an employer, owner or occupier under the Regulatory Reform (Fire Safety) Order 2005.
If records of existing firestopping do not exist, a fire compartmentation survey can establish the current position by identifying, photographing and locating breaches in fire-rated walls, floors and risers.